Does a split system need its own circuit? The electrical side of an install
9 min readUpdated Reviewed by Tom, owner and licensed electrician, on
A split system is two units: an indoor unit (usually on the wall) and an outdoor unit outside, joined by refrigerant pipes and cabling. This guide covers the electrical side of installing one in a Queensland home: the circuit, the breaker, the isolator, the switchboard and the paperwork, with each requirement traced to the manufacturer manual or regulation that sets it.
The short answer
Yes, if its installation manual says so, as Mitsubishi Electric's Australian manuals do: they ask for an exclusive circuit from the switchboard with no other appliances on it. The breaker and cable are sized from the unit's manual, and a hardwired split also needs a lockable isolating switch beside the outdoor unit. In Queensland, that wiring is electrical work for a licensed electrician.
In this guide11 sections
The electrical side of a split system install
Why a split system gets its own circuit: manuals such as Mitsubishi Electric's ask for one
A dedicated circuit runs from its own breaker on the switchboard to one appliance and nothing else. Manufacturers such as Mitsubishi Electric ask for one. Mitsubishi Electric's Australian installation manual for its SUZ-M outdoor units tells installers to provide an exclusive circuit for the air conditioner and not to connect other electrical appliances to it. The same manual warns that a power circuit with insufficient capacity, or incomplete electrical work, could result in a fire or an electric shock.
The breaker and cable on that circuit are chosen for that one unit, from the figures in its manual, so a new split system is not simply tapped into an existing power point circuit. A power point beside where the indoor unit will go does not change that, because the manual asks for a circuit with nothing else on it. The manual for your exact model is the document the electrician works from.
Plug-in units vs hardwired splits: a plug is not a shortcut
In Mitsubishi Electric's SUZ-M manual, the wiring table lists an outdoor unit power supply, and a separate cable connects the outdoor unit to the indoor unit. That is a hardwired installation.
Some small units can be connected by a plug instead. Mitsubishi Electric's manual for its smallest wall models, the MSZ-AP15 and AP20, covers plugging the unit into an outlet, yet the same manual still asks for an exclusive circuit and says the wiring between the indoor and outdoor units must be installed by a licensed electrical contractor to comply with AS/NZS 3000. A plug changes how the unit is switched off for servicing, not who wires it or whether it shares a circuit.
The true plug-and-go option is a portable air conditioner. energy.gov.au notes that portables need an exhaust duct through an open window and are not as effective or as efficient as installed units.
Breaker and cable size: set by the install manual, not a rule of thumb
The right breaker for a split system is the one its installation manual specifies, and the figure rises with the size of the unit. In Mitsubishi Electric's SUZ-M manual, the M25 and M35 outdoor units take a 10 A breaker with supply wiring of at least 1.5 mm², and the M50, M60 and M71 units take 20 A with at least 2.5 mm². Fujitsu General's Australian field references list 10 A to 20 A across its KMCA wall splits, with 4.0 mm² power cable on the two largest models. Both brands call for earth leakage protection on the circuit.
That answers the 40 amp question that comes up in searches: none of these split system manuals lists anything near 40 A. These units run on a single phase 230 to 240 V supply. A bigger breaker is not an upgrade, because the manual sets breaker and cable as a pair, and Mitsubishi notes that wiring size must comply with local and national code. The table below shows the figures by model.
The outdoor isolator: required beside the unit
A hardwired split system needs an isolating switch next to the outdoor unit. Hager, an electrical equipment maker, summarises the AS/NZS 3000 wiring rules this way: every air conditioning and heat pump system needs an independent, lockable isolating switch installed adjacent to the unit but not on it, within about arm's length or 1.25 metres. The switch lets whoever services the unit turn the power off right there and lock it off while they work, instead of relying on a breaker at a board on the other side of the house.
Hager also notes the exception: a single air conditioner plugged into a readily accessible power point needs no other isolation, because pulling the plug does the same job. For a hardwired unit, the isolator is part of the electrical work. It is wired into the new circuit and mounted outdoors, so its position and type are chosen by the licensed electrician doing the install.
Switchboard checks before the new circuit goes in
A new air conditioner circuit starts at the switchboard, so the electrician checks three things on the board.
Spare space. The board needs room for the new breaker, or room made by rearranging or replacing parts of it.
A safety switch on the power points. Under section 30 of Queensland's Electrical Safety Regulation 2026, a licensed electrician must not do electrical installation work in a home unless a safety switch protects the general purpose power points, or the job includes fitting one. The regulation lists limited exceptions, such as emergency or safety work, but unless one of those exceptions applies, a home without one gets one as part of the work.
Protection for the new circuit itself. Australian electrical regulators, through the Electrical Regulatory Authorities Council, say that when one circuit is altered, only that circuit must get RCD protection. Replacing the whole board is a separate decision, and a new board brings RCD protection for every applicable circuit on it.
Who does which part: an electrical licence and a refrigerant licence
A split system install needs two kinds of licence, and they cover different parts of the job. The electrical side, meaning the new circuit, the breaker, the isolator and the cable between the units, is electrical work. Queensland's Electrical Safety Office says appliances that need to be hard-wired must be connected by a licensed electrician, and that a business doing electrical work for others must hold an electrical contractor licence.
The refrigerant side is separate. energy.gov.au says all air conditioner installers must be licensed through the Australian Refrigeration Council, and the ARC describes its refrigerant handling licence as a national environmental licence, with electrical licensing left to each state. One licence does not cover the other.
Ask any installer for both numbers, and check the electrical contractor licence on the Electrical Safety Office's Electrical Licence Search. Tom's Air Conditioning & Electrical holds Queensland electrical contractor licence REC 13541.
The certificate after the electrical work: ask for it
Once the new circuit is connected, you should receive a certificate of testing and compliance. Section 229 of the Electrical Safety Regulation 2026 requires the licensed electrical contractor who connects the work to give the customer this certificate as soon as practicable after the connection.
The certificate names the installation tested, the date of the test and the contractor's licence number. It certifies that the installation, as far as the new work affected it, was tested to make sure it is electrically safe and complies with the wiring rules, AS/NZS 3000. The contractor must keep a copy for at least five years.
Keep your copy with the split system's manual and warranty papers. It is the written record that a licensed contractor tested the new work for electrical safety and compliance with the wiring rules.
What you can do yourself before the install: plan, not wire
An owner can do the planning, not the wiring. The Electrical Safety Office says DIY electrical work is unlicensed and illegal in Queensland, and electrical work under section 18 of the Electrical Safety Act 2002 includes installing and altering electrical equipment. That covers running the circuit, fitting the isolator and connecting either unit. The DIY part stops there.
Before you ask for a quote, gather what the installer will want to see: a photo of the switchboard, and the model number of the unit you are considering, so the installer can read its manual. The office notes that cutting openings for air conditioning units is not itself electrical work, but wiring inside wall cavities is a risk, so leave wall penetrations to the installer as well. The Energy Rating site suggests asking installers about placement and any electrical work that may be needed.
Read the split system installation cost guide
When to call a licensed electrician: call Tom on 0401 456 987.
At a glance
Scroll the table sideways to see every column.
| Factor | Breaker | Supply cable | Earth leakage protection |
|---|---|---|---|
| Mitsubishi Electric SUZ-M25, M35 | 10 A | 1.5 mm² minimum | Earth leakage breaker |
| Mitsubishi Electric SUZ-M50, M60, M71 | 20 A | 2.5 mm² minimum | Earth leakage breaker |
| Fujitsu General KMCA model 09 | 10 A | Not listed in the field reference | 30 mA |
| Fujitsu General KMCA models 12 and 18 | 16 A | 2.5 mm² (model 18) | 30 mA |
| Fujitsu General KMCA models 22 and 24 | 20 A | 4.0 mm² | 30 mA |
Common questions
What size circuit breaker does a split system need?
The size its installation manual specifies, which rises with the unit's capacity. Mitsubishi Electric's SUZ-M manual lists a 10 A breaker for its M25 and M35 outdoor units and 20 A for the M50 to M71 units. Fujitsu General's KMCA references run from 10 A to 20 A across its wall splits. The cable is sized with the breaker, so the electrician reads both from the manual for your exact model rather than picking a standard figure.
Can a split system be plugged into a normal power point?
Only if its manual allows a plug connection, and that manual may still ask for a circuit of its own. Mitsubishi Electric's manual for its smallest MSZ-AP wall units covers a plug connection but still asks for an exclusive circuit with nothing else on it, and says the wiring between the indoor and outdoor units must be installed by a licensed electrical contractor. For units like these, a plug changes how the unit is switched off, not whether the manual asks for its own circuit.
Does a split system need an outdoor isolator in Queensland?
Yes, for a hardwired unit. The AS/NZS 3000 wiring rules, as summarised by Hager, call for an independent lockable isolating switch adjacent to the outdoor unit but not mounted on it, within about 1.25 metres. It lets the unit be switched off and locked off at the unit for servicing. A single unit plugged into a readily accessible power point is the exception, because the plug provides the isolation.
Who is allowed to wire a split system in Queensland?
A licensed electrician working for a licensed electrical contractor. The Electrical Safety Office says hard-wired appliances must be connected by a licensed electrician and that DIY electrical work is illegal in Queensland. The refrigerant pipework is a separate job that needs an Australian Refrigeration Council licence. Check the electrical contractor licence on the Electrical Licence Search before work starts. Tom's Air Conditioning & Electrical holds licence REC 13541.
Do older homes in Pine Rivers need a switchboard upgrade before a split system goes in?
Not automatically. The board needs a spare space for the new breaker, and under section 30 of the Electrical Safety Regulation 2026 the power points must have a safety switch or the job must include fitting one, unless an exception applies. Regulators say only the new or altered circuit needs RCD protection. Replacing the whole board is a separate decision. Tom covers Pine Rivers from his base in Warner.
Something not covered? Call Tom on 0401 456 987.
Sources
- Installation manual, SUZ-M25 to M71 VAD-A outdoor unitsMitsubishi Electric Australia. Accessed .
- Installation manual, MSZ-AP15 and AP20 wall unitsMitsubishi Electric Australia. Accessed .
- ASTG09KMCA / AOTG09KMCA installation referenceFujitsu General Australia support site. Accessed .
- ASTG18KMCA / AOTG18KMCA installation referenceFujitsu General Australia support site. Accessed .
- Isolation switch requirements (wiring rules)Hager Australia. Accessed .
A licence number you can look up
Reviewed by Tom, owner and licensed electrician (Queensland electrical contractor, licence REC 13541), on 2026-11-20.
Queensland Electrical Contractor
Registered electrical contractor in Queensland, licence REC 13541, listed on the Electrical Safety Office licence search.
Check the licenceSmoke alarm compliance
Smoke alarm installs to the Queensland legislation: photoelectric, interconnected, and to AS 3786.
Read the Queensland rules